Signal & Communication

    What voltage should a DALI bus have, and how do I measure it?

    By Lichtvision Engineering · Published

    Short answer

    An idle DALI bus normally reads around 16 V DC. IEC 62386-101 allows an idle bus voltage between 9.5 V and 22.5 V, and the bus power supply limits the current to a maximum of 250 mA. Measure in DC mode directly at the DALI terminals while there is no traffic on the line. A reading of 0 V means no bus power supply is active; a reading below 9.5 V points to an overload, a short circuit or too much voltage drop along the line. ProbitSite shows the bus voltage in volts and indicates whether it lies within the valid range.

    The values from the standard

    IEC 62386-101 sets the electrical framework for every DALI line. The nominal bus voltage is 16 V DC. In the idle state, the voltage on the line must lie between 9.5 V and 22.5 V. The bus power supply limits its output current to 250 mA. Every connected device draws a small current from the bus, so the supply must be sized for everything on the line. Along the cable, the voltage may drop by no more than 2 V, which in practice limits a line to about 300 m.

    How to measure it correctly

    Set the multimeter to DC voltage and connect the probes to DA+ and DA− at a terminal or junction. Take the reading while the bus is idle: DALI transmits data by briefly pulling the line low, so the value jumps during traffic. Measure once next to the bus power supply and once at the far end of the longest run. The difference between the two readings is the voltage drop along the cable. Always treat the DALI line as a mains-voltage line: the bus is not SELV, and only trained personnel may connect to it.

    What the reading tells you

    A reading of 0 V means that no bus power supply is feeding the line, the supply is switched off, or the cable is interrupted between the supply and your measuring point. A reading below 9.5 V usually means the supply is overloaded by too many devices, a device or a wiring fault is pulling the line down, or the line is too long for its cross-section. A reading above 22.5 V points to a supply that does not comply with the standard. Mains voltage on the DALI terminals is a dangerous wiring fault: disconnect the installation and correct the wiring before doing anything else. If the voltage is within range but communication is still unreliable, the cause lies elsewhere; see I measure a DALI voltage but communication is unreliable, how do I fix it?

    How ProbitSite helps

    ProbitSite shows the DALI bus voltage in volts on its start screen and indicates whether it lies within the valid range, so you do not need a separate multimeter for this check. If it detects no bus voltage at all, it switches on its integrated bus power supply, which lets you scan and test a line before the system's own supply is installed. The scan then goes beyond voltage and rates the signal quality of every device from the bit timing of its responses.

    bus voltage16 V9.5–22.5 V250 mAvoltage dropbus power supplymeasurement

    Diagnose DALI issues like this in seconds

    ProbitSite is the DALI-2 certified handheld multimeter built for exactly this kind of on-site fault finding.

    Related cases